Replacement Components for Surgelogic™ Power-Zone™ 4 Switchgear IMA Surge Protective Devices.
Issue:
What components should be used as replacements for Power-Zone™ 4 Switchgear IMA series Surge Protective Devices?
Product Line:
Surge Protective Devices (SPDs)
Environment:
Power-Zone™ 4 Switchgear IMA surge protective devices.
Cause:
Replacement or Repair Parts
Resolution:
To find the right replacement parts for your Power-Zone™ 4 Switchgear IMA series Surge Protective Devices (SPDs), refer to the Replacement Component Selector Table provided below. You can also find an example of a typical product label and catalog number at the end of this article.
Replacement Component Matrix
Surgelogic Label
To find your SPD part #, locate a white Surgelogic sticker on the interior of your SPD. This can typically be found on the sidewalls or on the door of the SPD. The label will look like the following:
What components should be used as replacements for Power-Zone™ 4 Switchgear IMA series Surge Protective Devices?
Product Line:
Surge Protective Devices (SPDs)
Environment:
Power-Zone™ 4 Switchgear IMA surge protective devices.
Cause:
Replacement or Repair Parts
Resolution:
To find the right replacement parts for your Power-Zone™ 4 Switchgear IMA series Surge Protective Devices (SPDs), refer to the Replacement Component Selector Table provided below. You can also find an example of a typical product label and catalog number at the end of this article.
Replacement Component Matrix
| Catalog Number | Peak Surge Current | Module Catalog Number "A" Phase | Module Catalog Number "B" Phase | Module Catalog Number "C" Phase | Diagnostic Cable (3 per kit) | Front Display (NEMA 1 SPDs only) |
| TVS1IMA12Z | 120kA | MA1IMA12 | N/A | MA1IMA12 | TVS192PCK | TVS1DSPHC |
| TVS1IMA12Z1 | 120kA | MA1IMA121 | N/A | MA1IMA121 | TVS192PCK | TVS1DSPHC |
| TVS1IMA16Z | 160kA | MA1IMA16 | N/A | MA1IMA16 | TVS192PCK | TVS1DSPHC |
| TVS1IMA16Z1 | 160kA | MA1IMA161 | N/A | MA1IMA161 | TVS192PCK | TVS1DSPHC |
| TVS1IMA24Z | 240kA | MA1IMA24 | N/A | MA1IMA24 | TVS192PCK | TVS1DSPHC |
| TVS1IMA24Z1 | 240kA | MA1IMA241 | N/A | MA1IMA241 | TVS192PCK | TVS1DSPHC |
| TVS1IMA32Z | 320kA | MA1IMA16 (2 Modules Required) | N/A | MA1IMA16 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS1IMA32Z1 | 320kA | MA1IMA161 (2 Modules Required) | N/A | MA1IMA161 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS1IMA48Z | 480kA | MA1IMA24 (2 Modules Required) | N/A | MA1IMA24 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS1IMA48Z1 | 480kA | MA1IMA241 (2 Modules Required) | N/A | MA1IMA241 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS2IMA12Z | 120kA | MA1IMA12 | MA1IMA12 | MA1IMA12 | TVS192PCK | TVS3DSPHC |
| TVS2IMA12Z1 | 120kA | MA1IMA121 | MA1IMA121 | MA1IMA121 | TVS192PCK | TVS3DSPHC |
| TVS2IMA16Z | 160kA | MA1IMA16 | MA1IMA16 | MA1IMA16 | TVS192PCK | TVS3DSPHC |
| TVS2IMA16Z1 | 160kA | MA1IMA161 | MA1IMA161 | MA1IMA161 | TVS192PCK | TVS3DSPHC |
| TVS2IMA24Z | 240kA | MA1IMA24 | MA1IMA24 | MA1IMA24 | TVS192PCK | TVS3DSPHC |
| TVS2IMA24Z1 | 240kA | MA1IMA241 | MA1IMA241 | MA1IMA241 | TVS192PCK | TVS3DSPHC |
| Catalog Number | Peak Surge Current | Module Catalog Number "A" Phase | Module Catalog Number "B" Phase | Module Catalog Number "C" Phase | Diagnostic Cable (3 per kit) | Front Display (NEMA 1 SPDs only) |
| TVS2IMA32Z | 320kA | MA1IMA16 (2 Modules Required) | MA1IMA16 (2 Modules Required) | MA1IMA16 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS2IMA32Z1 | 320kA | MA1IMA161 (2 Modules Required) | MA1IMA161 (2 Modules Required) | MA1IMA161 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS2IMA48Z | 480kA | MA1IMA24 (2 Modules Required) | MA1IMA24 (2 Modules Required) | MA1IMA24 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS2IMA48Z1 | 480kA | MA1IMA241 (2 Modules Required) | MA1IMA241 (2 Modules Required) | MA1IMA241 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS3IMA12Z | 120kA | MA1IMA12 | MA3IMA12 | MA1IMA12 | TVS192PCK | TVS3DSPHC |
| TVS3IMA12Z1 | 120kA | MA1IMA121 | MA3IMA121 | MA1IMA121 | TVS192PCK | TVS3DSPHC |
| TVS3IMA16Z | 160kA | MA1IMA16 | MA3IMA16 | MA1IMA16 | TVS192PCK | TVS3DSPHC |
| TVS3IMA16Z1 | 160kA | MA1IMA161 | MA3IMA161 | MA1IMA161 | TVS192PCK | TVS3DSPHC |
| TVS3IMA24Z | 240kA | MA1IMA24 | MA3IMA24 | MA1IMA24 | TVS192PCK | TVS3DSPHC |
| TVS3IMA24Z1 | 240kA | MA1IMA241 | MA3IMA241 | MA1IMA241 | TVS192PCK | TVS3DSPHC |
| TVS3IMA32Z | 320kA | MA1IMA16 (2 Modules Required) | MA3IMA16 (2 Modules Required) | MA1IMA16 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS3IMA32Z1 | 320kA | MA1IMA161 (2 Modules Required) | MA3IMA161 (2 Modules Required) | MA1IMA161 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS3IMA48Z | 480kA | MA1IMA24 (2 Modules Required) | MA3IMA24 (2 Modules Required) | MA1IMA24 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS3IMA48Z1 | 480kA | MA1IMA241 (2 Modules Required) | MA3IMA241 (2 Modules Required) | MA1IMA241 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS4IMA12Z | 120kA | MA4IMA12 | MA4IMA12 | MA4IMA12 | TVS192PCK | TVS3DSPHC |
| TVS4IMA12Z1 | 120kA | MA4IMA121 | MA4IMA121 | MA4IMA121 | TVS192PCK | TVS3DSPHC |
| TVS4IMA16Z | 160kA | MA4IMA16 | MA4IMA16 | MA4IMA16 | TVS192PCK | TVS3DSPHC |
| TVS4IMA16Z1 | 160kA | MA4IMA161 | MA4IMA161 | MA4IMA161 | TVS192PCK | TVS3DSPHC |
| TVS4IMA24Z | 240kA | MA4IMA24 | MA4IMA24 | MA4IMA24 | TVS192PCK | TVS3DSPHC |
| TVS4IMA24Z1 | 240kA | MA4IMA241 | MA4IMA241 | MA4IMA241 | TVS192PCK | TVS3DSPHC |
| TVS4IMA32Z | 320kA | MA4IMA16 (2 Modules Required) | MA4IMA16 (2 Modules Required) | MA4IMA16 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS4IMA32Z1 | 320kA | MA4IMA161 (2 Modules Required) | MA4IMA161 (2 Modules Required) | MA4IMA161 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| Catalog Number | Peak Surge Current | Module Catalog Number "A" Phase | Module Catalog Number "B" Phase | Module Catalog Number "C" Phase | Diagnostic Cable (3 per kit) | Front Display (NEMA 1 SPDs only) |
| TVS4IMA48Z | 480kA | MA4IMA24 (2 Modules Required) | MA4IMA24 (2 Modules Required) | MA4IMA24 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS4IMA48Z1 | 480kA | MA4IMA241 (2 Modules Required) | MA4IMA241 (2 Modules Required) | MA4IMA241 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS5IMA10Z | 100kA | MA5IMA10 | MA5IMA10 | MA5IMA10 | TVS192PCK | TVS3DSPHC |
| TVS5IMA10Z1 | 100kA | MA5IMA101 | MA5IMA101 | MA5IMA101 | TVS192PCK | TVS3DSPHC |
| TVS5IMA12Z | 120kA | MA5IMA12 | MA5IMA12 | MA5IMA12 | TVS192PCK | TVS3DSPHC |
| TVS5IMA12Z1 | 120kA | MA5IMA121 | MA5IMA121 | MA5IMA121 | TVS192PCK | TVS3DSPHC |
| TVS5IMA16Z | 160kA | MA5IMA16 | MA5IMA16 | MA5IMA16 | TVS192PCK | TVS3DSPHC |
| TVS5IMA16Z1 | 160kA | MA5IMA161 | MA5IMA161 | MA5IMA161 | TVS192PCK | TVS3DSPHC |
| TVS5IMA20Z | 200kA | MA5IMA20 | MA5IMA20 | MA5IMA20 | TVS192PCK | TVS3DSPHC |
| TVS5IMA20Z1 | 200kA | MA5IMA201 | MA5IMA201 | MA5IMA201 | TVS192PCK | TVS3DSPHC |
| TVS5IMA24Z | 240kA | MA5IMA24 | MA5IMA24 | MA5IMA24 | TVS192PCK | TVS3DSPHC |
| TVS5IMA24Z1 | 240kA | MA5IMA241 | MA5IMA241 | MA5IMA241 | TVS192PCK | TVS3DSPHC |
| TVS5IMA32Z | 320kA | MA5IMA16 (2 Modules Required) | MA5IMA16 (2 Modules Required) | MA5IMA16 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS5IMA32Z1 | 320kA | MA5IMA161 (2 Modules Required) | MA5IMA161 (2 Modules Required) | MA5IMA161 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS5IMA48Z | 480kA | MA5IMA24 (2 Modules Required) | MA5IMA24 (2 Modules Required) | MA5IMA24 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS5IMA48Z1 | 480kA | MA5IMA241 (2 Modules Required) | MA5IMA241 (2 Modules Required) | MA5IMA241 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS6IMA10Z | 100kA | MA6IMA10 | MA6IMA10 | MA6IMA10 | TVS192PCK | TVS3DSPHC |
| TVS6IMA10Z1 | 100kA | MA6IMA101 | MA6IMA101 | MA6IMA101 | TVS192PCK | TVS3DSPHC |
| TVS6IMA12Z | 120kA | MA6IMA12 | MA6IMA12 | MA6IMA12 | TVS192PCK | TVS3DSPHC |
| Catalog Number | Peak Surge Current | Module Catalog Number "A" Phase | Module Catalog Number "B" Phase | Module Catalog Number "C" Phase | Diagnostic Cable (3 per kit) | Front Display (NEMA 1 SPDs only) |
| TVS6IMA12Z1 | 120kA | MA6IMA121 | MA6IMA121 | MA6IMA121 | TVS192PCK | TVS3DSPHC |
| TVS6IMA16Z | 160kA | MA6IMA16 | MA6IMA16 | MA6IMA16 | TVS192PCK | TVS3DSPHC |
| TVS6IMA16Z1 | 160kA | MA6IMA161 | MA6IMA161 | MA6IMA161 | TVS192PCK | TVS3DSPHC |
| TVS6IMA20Z | 200kA | MA6IMA20 | MA6IMA20 | MA6IMA20 | TVS192PCK | TVS3DSPHC |
| TVS6IMA20Z1 | 200kA | MA6IMA201 | MA6IMA201 | MA6IMA201 | TVS192PCK | TVS3DSPHC |
| TVS6IMA24Z | 240kA | MA6IMA24 | MA6IMA24 | MA6IMA24 | TVS192PCK | TVS3DSPHC |
| TVS6IMA24Z1 | 240kA | MA6IMA241 | MA6IMA241 | MA6IMA241 | TVS192PCK | TVS3DSPHC |
| TVS6IMA32Z | 320kA | MA6IMA16 (2 Modules Required) | MA6IMA16 (2 Modules Required) | MA6IMA16 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS6IMA32Z1 | 320kA | MA6IMA161 (2 Modules Required) | MA6IMA161 (2 Modules Required) | MA6IMA161 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS6IMA48Z | 480kA | MA6IMA24 (2 Modules Required) | MA6IMA24 (2 Modules Required) | MA6IMA24 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS6IMA48Z1 | 480kA | MA6IMA241 (2 Modules Required) | MA6IMA241 (2 Modules Required) | MA6IMA241 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS9IMA10Z | 100kA | MA9IMA10 | MA9IMA10 | MA9IMA10 | TVS192PCK | TVS3DSPHC |
| TVS9IMA10Z1 | 100kA | MA9IMA101 | MA9IMA101 | MA9IMA101 | TVS192PCK | TVS3DSPHC |
| TVS9IMA12Z | 120kA | MA9IMA12 | MA9IMA12 | MA9IMA12 | TVS192PCK | TVS3DSPHC |
| TVS9IMA12Z1 | 120kA | MA9IMA121 | MA9IMA121 | MA9IMA121 | TVS192PCK | TVS3DSPHC |
| TVS9IMA16Z | 160kA | MA9IMA16 | MA9IMA16 | MA9IMA16 | TVS192PCK | TVS3DSPHC |
| TVS9IMA16Z1 | 160kA | MA9IMA161 | MA9IMA161 | MA9IMA161 | TVS192PCK | TVS3DSPHC |
| TVS9IMA20Z | 200kA | MA9IMA10 (2 Modules Required) | MA9IMA10 (2 Modules Required) | MA9IMA10 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS9IMA20Z1 | 200kA | MA9IMA101 (2 Modules Required) | MA9IMA101 (2 Modules Required) | MA9IMA101 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS9IMA24Z | 240kA | MA9IMA12 (2 Modules Required) | MA9IMA12 (2 Modules Required) | MA9IMA12 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS9IMA24Z1 | 240kA | MA9IMA121 (2 Modules Required) | MA9IMA121 (2 Modules Required) | MA9IMA121 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS9IMA32Z | 320kA | MA9IMA16 (2 Modules Required) | MA9IMA16 (2 Modules Required) | MA9IMA16 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS9IMA32Z1 | 320kA | MA9IMA161 (2 Modules Required) | MA9IMA161 (2 Modules Required) | MA9IMA161 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS9IMA48Z | 480kA | MA9IMA24 (2 Modules Required) | MA9IMA24 (2 Modules Required) | MA9IMA24 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
| TVS9IMA48Z1 | 480kA | MA9IMA241 (2 Modules Required) | MA9IMA241 (2 Modules Required) | MA9IMA241 (2 Modules Required) | TVS192PCK (2 Kits Required) | TVS6DSPHC |
Surgelogic Label
To find your SPD part #, locate a white Surgelogic sticker on the interior of your SPD. This can typically be found on the sidewalls or on the door of the SPD. The label will look like the following:
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.