Replacement Components for Surgelogic™ 480Y/277V 3 Ø, HRG, 3-Wire+G Legacy EMA Series Surge Protective Devices

Issue:
What are the replacement components for 480Y/277V 3-Phase, HRG (High Resistance Grounding), 3-Wire+Ground Legacy EMA Series Surge Protective Devices?

Product Line:
Surge Protective Devices (SPDs)

Environment:
480Y/277V 3 Ø, HRG, 3-wire+G Legacy EMA surge protective devices.

Cause:
Replacement or Repair Parts

Resolution:
To determine the correct Replacement parts to purchase for your 480Y/277V 3 Ø, HRG, 3-wire+G Legacy EMA Series Surge Protective Devices (SPDs), see the Replacement Component Selector Table below. An example of a typical product label and catalog number is at the end of this article.

Replacement Component Matrix
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4HEMA10A100kAMA4IMA10HMA4IMA10HMA4IMA10HTVS36PCKTVS3DSPHC
TVS4HEMA10ASWT100kAMA4IMA10HMA4IMA10HMA4IMA10HTVS36PCKTVS3DSPHC
TVS4HEMA10A1100kAMA4IMA10H1MA4IMA10H1MA4IMA10H1TVS36PCKTVS3DSPHC
TVS4HEMA10AI100kAMA4IMA10HMA4IMA10HMA4IMA10HTVS36PCKTVS3DSPHC
TVS4HEMA10AISWT100kAMA4IMA10HMA4IMA10HMA4IMA10HTVS36PCKTVS3DSPHC
TVS4HEMA10AISWT1100kAMA4IMA10H1MA4IMA10H1MA4IMA10H1TVS36PCKTVS3DSPHC
TVS4HEMA10AI1100kAMA4IMA10H1MA4IMA10H1MA4IMA10H1TVS36PCKTVS3DSPHC
TVS4HEMA10S100kAMA4IMA10HMA4IMA10HMA4IMA10HTVS36PCKTVS3DSPHC
TVS4HEMA10SI100kAMA4IMA10HMA4IMA10HMA4IMA10HTVS36PCKTVS3DSPHC
TVS4HEMA10SSWT100kAMA4IMA10HMA4IMA10HMA4IMA10HTVS36PCKTVS3DSPHC
TVS4HEMA10ASWT1100kAMA4IMA10H1MA4IMA10H1MA4IMA10H1TVS36PCKTVS3DSPHC
TVS4HEMA10SISWT100kAMA4IMA10HMA4IMA10HMA4IMA10HTVS36PCKTVS3DSPHC
TVS4HEMA10S1100kAMA4IMA10H1MA4IMA10H1MA4IMA10H1TVS36PCKTVS3DSPHC
TVS4HEMA10SSWT1100kAMA4IMA10H1MA4IMA10H1MA4IMA10H1TVS36PCKTVS3DSPHC
TVS4HEMA10SI1100kAMA4IMA10H1MA4IMA10H1MA4IMA10H1TVS36PCKTVS3DSPHC
TVS4HEMA10SISWT1100kAMA4IMA10H1MA4IMA10H1MA4IMA10H1TVS36PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4HEMA12A120kAMA4IMA12HMA4IMA12HMA4IMA12HTVS36PCKTVS3DSPHC
TVS4HEMA12ASWT120kAMA4IMA12HMA4IMA12HMA4IMA12HTVS36PCKTVS3DSPHC
TVS4HEMA12A1120kAMA4IMA12H1MA4IMA12H1MA4IMA12H1TVS36PCKTVS3DSPHC
TVS4HEMA12AI120kAMA4IMA12HMA4IMA12HMA4IMA12HTVS36PCKTVS3DSPHC
TVS4HEMA12AISWT120kAMA4IMA12HMA4IMA12HMA4IMA12HTVS36PCKTVS3DSPHC
TVS4HEMA12AISWT1120kAMA4IMA12H1MA4IMA12H1MA4IMA12H1TVS36PCKTVS3DSPHC
TVS4HEMA12AI1120kAMA4IMA12H1MA4IMA12H1MA4IMA12H1TVS36PCKTVS3DSPHC
TVS4HEMA12S120kAMA4IMA12HMA4IMA12HMA4IMA12HTVS36PCKTVS3DSPHC
TVS4HEMA12SI120kAMA4IMA12HMA4IMA12HMA4IMA12HTVS36PCKTVS3DSPHC
TVS4HEMA12SSWT120kAMA4IMA12HMA4IMA12HMA4IMA12HTVS36PCKTVS3DSPHC
TVS4HEMA12ASWT1120kAMA4IMA12H1MA4IMA12H1MA4IMA12H1TVS36PCKTVS3DSPHC
TVS4HEMA12SISWT120kAMA4IMA12HMA4IMA12HMA4IMA12HTVS36PCKTVS3DSPHC
TVS4HEMA12S1120kAMA4IMA12H1MA4IMA12H1MA4IMA12H1TVS36PCKTVS3DSPHC
TVS4HEMA12SSWT1120kAMA4IMA12H1MA4IMA12H1MA4IMA12H1TVS36PCKTVS3DSPHC
TVS4HEMA12SI1120kAMA4IMA12H1MA4IMA12H1MA4IMA12H1TVS36PCKTVS3DSPHC
TVS4HEMA12SISWT1120kAMA4IMA12H1MA4IMA12H1MA4IMA12H1TVS36PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4HEMA16A160kAMA4IMA16HMA4IMA16HMA4IMA16HTVS36PCKTVS3DSPHC
TVS4HEMA16ASWT160kAMA4IMA16HMA4IMA16HMA4IMA16HTVS36PCKTVS3DSPHC
TVS4HEMA16A1160kAMA4IMA16H1MA4IMA16H1MA4IMA16H1TVS36PCKTVS3DSPHC
TVS4HEMA16AI160kAMA4IMA16HMA4IMA16HMA4IMA16HTVS36PCKTVS3DSPHC
TVS4HEMA16AISWT160kAMA4IMA16HMA4IMA16HMA4IMA16HTVS36PCKTVS3DSPHC
TVS4HEMA16AISWT1160kAMA4IMA16H1MA4IMA16H1MA4IMA16H1TVS36PCKTVS3DSPHC
TVS4HEMA16AI1160kAMA4IMA16H1MA4IMA16H1MA4IMA16H1TVS36PCKTVS3DSPHC
TVS4HEMA16S160kAMA4IMA16HMA4IMA16HMA4IMA16HTVS36PCKTVS3DSPHC
TVS4HEMA16SI160kAMA4IMA16HMA4IMA16HMA4IMA16HTVS36PCKTVS3DSPHC
TVS4HEMA16SSWT160kAMA4IMA16HMA4IMA16HMA4IMA16HTVS36PCKTVS3DSPHC
TVS4HEMA16ASWT1160kAMA4IMA16H1MA4IMA16H1MA4IMA16H1TVS36PCKTVS3DSPHC
TVS4HEMA16SISWT160kAMA4IMA16HMA4IMA16HMA4IMA16HTVS36PCKTVS3DSPHC
TVS4HEMA16S1160kAMA4IMA16H1MA4IMA16H1MA4IMA16H1TVS36PCKTVS3DSPHC
TVS4HEMA16SSWT1160kAMA4IMA16H1MA4IMA16H1MA4IMA16H1TVS36PCKTVS3DSPHC
TVS4HEMA16SI1160kAMA4IMA16H1MA4IMA16H1MA4IMA16H1TVS36PCKTVS3DSPHC
TVS4HEMA16SISWT1160kAMA4IMA16H1MA4IMA16H1MA4IMA16H1TVS36PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4HEMA20A200kAMA4IMA20HMA4IMA20HMA4IMA20HTVS36PCKTVS3DSPHC
TVS4HEMA20ASWT200kAMA4IMA20HMA4IMA20HMA4IMA20HTVS36PCKTVS3DSPHC
TVS4HEMA20A1200kAMA4IMA20H1MA4IMA20H1MA4IMA20H1TVS36PCKTVS3DSPHC
TVS4HEMA20AI200kAMA4IMA20HMA4IMA20HMA4IMA20HTVS36PCKTVS3DSPHC
TVS4HEMA20AISWT200kAMA4IMA20HMA4IMA20HMA4IMA20HTVS36PCKTVS3DSPHC
TVS4HEMA20AISWT1200kAMA4IMA20H1MA4IMA20H1MA4IMA20H1TVS36PCKTVS3DSPHC
TVS4HEMA20AI1200kAMA4IMA20H1MA4IMA20H1MA4IMA20H1TVS36PCKTVS3DSPHC
TVS4HEMA20S200kAMA4IMA20HMA4IMA20HMA4IMA20HTVS36PCKTVS3DSPHC
TVS4HEMA20SI200kAMA4IMA20HMA4IMA20HMA4IMA20HTVS36PCKTVS3DSPHC
TVS4HEMA20SSWT200kAMA4IMA20HMA4IMA20HMA4IMA20HTVS36PCKTVS3DSPHC
TVS4HEMA20ASWT1200kAMA4IMA20H1MA4IMA20H1MA4IMA20H1TVS36PCKTVS3DSPHC
TVS4HEMA20SISWT200kAMA4IMA20HMA4IMA20HMA4IMA20HTVS36PCKTVS3DSPHC
TVS4HEMA20S1200kAMA4IMA20H1MA4IMA20H1MA4IMA20H1TVS36PCKTVS3DSPHC
TVS4HEMA20SSWT1200kAMA4IMA20H1MA4IMA20H1MA4IMA20H1TVS36PCKTVS3DSPHC
TVS4HEMA20SI1200kAMA4IMA20H1MA4IMA20H1MA4IMA20H1TVS36PCKTVS3DSPHC
TVS4HEMA20SISWT1200kAMA4IMA20H1MA4IMA20H1MA4IMA20H1TVS36PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4HEMA24A240kAMA4IMA24HMA4IMA24HMA4IMA24HTVS36PCKTVS3DSPHC
TVS4HEMA24ASWT240kAMA4IMA24HMA4IMA24HMA4IMA24HTVS36PCKTVS3DSPHC
TVS4HEMA24A1240kAMA4IMA24H1MA4IMA24H1MA4IMA24H1TVS36PCKTVS3DSPHC
TVS4HEMA24AI240kAMA4IMA24HMA4IMA24HMA4IMA24HTVS36PCKTVS3DSPHC
TVS4HEMA24AISWT240kAMA4IMA24HMA4IMA24HMA4IMA24HTVS36PCKTVS3DSPHC
TVS4HEMA24AISWT1240kAMA4IMA24H1MA4IMA24H1MA4IMA24H1TVS36PCKTVS3DSPHC
TVS4HEMA24AI1240kAMA4IMA24H1MA4IMA24H1MA4IMA24H1TVS36PCKTVS3DSPHC
TVS4HEMA24S240kAMA4IMA24HMA4IMA24HMA4IMA24HTVS36PCKTVS3DSPHC
TVS4HEMA24SI240kAMA4IMA24HMA4IMA24HMA4IMA24HTVS36PCKTVS3DSPHC
TVS4HEMA24SSWT240kAMA4IMA24HMA4IMA24HMA4IMA24HTVS36PCKTVS3DSPHC
TVS4HEMA24ASWT1240kAMA4IMA24H1MA4IMA24H1MA4IMA24H1TVS36PCKTVS3DSPHC
TVS4HEMA24SISWT240kAMA4IMA24HMA4IMA24HMA4IMA24HTVS36PCKTVS3DSPHC
TVS4HEMA24S1240kAMA4IMA24H1MA4IMA24H1MA4IMA24H1TVS36PCKTVS3DSPHC
TVS4HEMA24SSWT1240kAMA4IMA24H1MA4IMA24H1MA4IMA24H1TVS36PCKTVS3DSPHC
TVS4HEMA24SI1240kAMA4IMA24H1MA4IMA24H1MA4IMA24H1TVS36PCKTVS3DSPHC
TVS4HEMA24SISWT1240kAMA4IMA24H1MA4IMA24H1MA4IMA24H1TVS36PCKTVS3DSPHC
Catalog NumberPeak Surge CurrentModule Catalog Number
"A" Phase
Module Catalog Number
"B" Phase
Module Catalog Number
"C" Phase
Diagnostic Cable
(3 per kit)
Front Display
(NEMA 1 SPDs only)
TVS4HEMA32A320kAMA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32ASWT320kAMA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32A1320kAMA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32AI320kAMA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32AISWT320kAMA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32AISWT1320kAMA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32AI1320kAMA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32S320kAMA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32SI320kAMA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32SSWT320kAMA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32ASWT1320kAMA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32SISWT320kAMA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)MA4IMA16H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32S1320kAMA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32SSWT1320kAMA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32SI1320kAMA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA32SISWT1320kAMA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)MA4IMA16H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48A480kAMA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48ASWT480kAMA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48A1480kAMA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48AI480kAMA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48AISWT480kAMA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48AISWT1480kAMA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48AI1480kAMA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48S480kAMA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48SI480kAMA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48SSWT480kAMA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48ASWT1480kAMA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48SISWT480kAMA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)MA4IMA24H (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48S1480kAMA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48SSWT1480kAMA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48SI1480kAMA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC
TVS4HEMA48SISWT1480kAMA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)MA4IMA24H1 (2 Modules Required)TVS36PCK (2 Kits Required)TVS6DSPHC


Surgelogic Label

To find your SPD part #, locate a white Surgelogic sticker on the interior of your SPD. This can typically be found on the sidewalls or on the door of the SPD. The label will look like the following:

tvss

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.