Where can I disable alarms using ION Setup
Issue
Where can I disable alarms using ION Setup?
Product Line
ION Setup
Environment
ION Meters
PowerLogic Meters
Cause
Alarms can be set up onboard a meter or through software; such as through ION Setup and PME.
Resolution
Disable alarms via ION Setup
If looking to disable an alarm for an ION meter, Advanced mode will need to be used, follow the instructions below:
Connect to device
Hold Ctrl+left click meter
Navigate to the Setpoint module folder
There are multiple ways to disable it:
Hold Ctrl+left click meter
Navigate to the Setpoint module folder
There are multiple ways to disable it:
- Unlink the Source register
- Open Module
- Under the Input tab, select Source and delete
- Click Ok, then click Send. Now the Setpoint module is disabled, since there is no source register linked.
- Delete the Setpoint module entirely
- Link the Input register to a boolean OFF value. if the Enable Setup register is set to Disabled, this input is ignored and the module is disabled. Disabling the module forces the Status output register to Not Available, overriding the Setpoint condition. For example, an external Boolean module can be used as a switch to define an OFF value to disable the Setpoint module, see ION Reference document for details.
If looking to disable an alarm for a PowerLogic meter, follow the instructions below:
Connect to device
Open Alarming module or Onboard alarms/events (depending on the model type)
Select the type of alarm
Uncheck the Enable box
Click ok, then Click send
The alarm has now been disabled
Open Alarming module or Onboard alarms/events (depending on the model type)
Select the type of alarm
Uncheck the Enable box
Click ok, then Click send
The alarm has now been disabled