Are the Powerpact B-Frame available with ground fault protection?
Issue:
Is there a Ground Fault option for Powerpact B-Frame?

Product Line:
Circuit breaker

Environment:
Powerpact B-Frame

Resolution:
B frame breaker alone does not have any capability for the Ground Fault Protection
Options are:
​- Use a Ground fault relay and a shunt trip with the B-Frame breaker
- Consider using an H-Frame breaker