How can the ATV340 be programmed for 2-wire control?

Article available in these languages:

  • Spanish

Resolution:
To configure the ATV340 for 2-wire control:

  1. From the Main Menu, select Complete Settings.
  2. Navigate to Command and Reference.
  3. Select 2/3-Wire Control.
  4. Set the control mode to 2-Wire Control (2C).

After enabling 2-wire control, you can select the desired 2-Wire Type:

  • Transition Control (default)
  • Level Control

Understanding the 2-Wire Control Types

Transition Control

  • The drive must be powered up before a run command is issued.
  • If a run input is already active when power is applied, the drive will not start until the command is cycled.

Level Control

  • The drive starts whenever a valid run command is present.
  • If the run command remains active during power-up, the drive will automatically start when power is restored.
  • If no run command is active, the drive remains in RDY (Ready) status until a run command is received.
Important Safety Notice:
Level Control may cause the motor to restart automatically after a power cycle or power restoration if the run command remains active. Verify that this behavior is safe and appropriate for your application before enabling this control mode.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings