What are the field installable equipment grounding kits and the grounding terminal data for light duty, general duty, heavy duty, and double throw safety switches?

Issue:
Part numbers and ground kit terminal lug data for all safety switch equipment / service grounding kits.

Product Line:
Enclosed Safety Switches

Resolution:
See the below tables for the field installable equipment grounding kits for the light duty, general duty, heavy duty, and double throw safety switches. Please read all applicable footnotes.
Light and General Duty Switch Equipment Grounding Kits
Switch Ampere RatingCatalog NumberLug Wire Range (AWG)
30 [1]Std.(1) 14 - 10 Cu or (1) 12 - 8 Al
30PK3GTA1(3) 14 - 4 Cu or (3) 12 - 4 Al or (6) 14 - 12 Cu or (6) 12 - 10 Al
60 [2]GTK03(2) 14 - 4 Cu or (2) 12 - 4 Al or (4) 14 - 12 Cu or (4) 12 - 10 Al
100GTK0610(2) 14 - 1/0 Cu or (2) 12 - 1/0 Al or (2) 14 - 6 Cu or (2) 12 - 6 Al
200PKOGTA2(2) 10 - 2/0 Cu or (2) 6 - 2/0 Cu Al
400, 600PKOGTA2 [3](2) 10 - 2/0 Cu or (2) 6 - 2/0 Cu Al
800PKOGTA3(6) 6 - 3/0 Al/Cu Max.
[1] Light duty safety switches.
[2] 60 A non-fusible switches accept PK3GTA1.
[3] Two required if ground conductors are run in parallel.
Heavy Duty Switch Equipment Grounding Kits [4] [5] [6]
Switch Ampere RatingSwitch Series NumberCatalog NumberLug Wire Range (AWG/kcmil)Copper Only Grounding KitCopper Only Kit Lug Wire Range (AWG/kcmil)
30F5-F6GTK03 [7](2) 14-4 Cu or (2) 12-4 Al or (4) 14-12 Cu or (4) 12-10 AlGTK03C [7] [8](2) 14-6 Cu
60F5-F6 (600 V)GTK0610(2) 14-1/0 Cu or (2) 12-1/0 Al
and
(2) 14-6 Cu or (2) 12-6 Al
GTK0610C(2) 14-1/0 Cu and (2) 14-6 Cu
60F5-F6 (240 V)GTK03(2) 14-4 Cu or (2) 12-4 Al or (4) 14-12 Cu or (4) 12-10 AlGTK03C(2) 14-6 Cu
100F5-F6GTK0610(2) 14-1/0 Cu or (2) 12-1/0 Al and (2) 14-6 Cu or (2) 12-6 AlGTK0610C(2) 14-1/0 Cu and (2) 14-6 Cu
200F5-F6PKOGTA2(2) 10-2/0 Cu or (2) 6-2/0 AlPKOGTC2(2) 14-4 Cu
400, 600E4-E5PKOGTA2 [9](2) 10-2/0 Cu or (2) 6-2/0 AlPKOGTC3(4) 14-1/0 Cu
800E4PKOGTA7(4) 4-350 Al/Cu--
1200E4PKOGTA8(8) 4-350 Al/Cu--
[4] Equipment grounding kits are also available factory installed for Heavy Duty Safety Switches.  For factory installation, add suffix GL to standard switch catalog number.  Example:  H361GL.
[5] For series not shown in table refer to the switch wiring diagram.
[6] Equipment Ground Kits (Al/Cu) are factory installed standard in 30-200 A Series F NEMA Type 4/4X/5 (stainless steel), 12 and 12K. Equipment Ground Kits are standard factory installed on all receptacle switches and all Series F 30-200 A, 4 and 6 pole switches.
[7] H2212AWK accepts GTK03 or GTK03C. H3612A or AWK accepts GTK03C. H3612 and H3612RB accepts GTK0610 HU3612AWK accepts GTK03C. HU3612A accepts GTK0610C.  HU3612RB accepts GTK0610 or GTK0610C.
[8] Optional copper equipment grounding kit for the 4 and 6 pole 30 A F Series: H461DS, H461AWK, HU461DS, HU661DS and HU661AWK accepts GTK03C HU461AWK accepts GTK0610C.
[9] Two required if equipment grounding conductors are run in parallel.

Double Throw Switch Equipment Grounding Kits
Switch Ampere Rating and TypeCatalog NumberLug Wire Range (AWG/kcmil)
30-60 A Type DT, DTU (Series F)Included(3) 14-2 Al/Cu or (6) 14-10 Al/Cu
100 A Type DT, DTU (Series F)Included(3) 14 - 1/0 Al/Cu
30 A Type 92,000 (Series T4)DT30SG(4) 14-4 Al/Cu
200 A Type 82000 and DTU (Series E)DT100SG(3) 14-1/0 Al/Cu
400 A Type 82000 (Series A)PKOGTA2 (2 required)(4) 10-2/0 Cu or (4) 6-2/0 Al
600 A Type DTU (Series A)DS468GKD(2) 6-250 Al/Cu [10]

[10] (3) 6-250 ground lugs are provided as standard. DS468GKD provides an additional (2) 6-250 ground lugs.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings