Why are ComPact NS/ PowerPact P, R breakers not available in the device selection list of Com’X 210/ 510?

Issue

Why are ComPact NS/ PowerPact P, R breakers not available in the device selection list of Com’X 210/ 510?

How to select a device profile for these breakers during commissioning process?
The ComPact NS/PowerPact P, R breakers discover as MasterPact breakers. ComPact NS/PowerPact P, R breakers do not appear in the device selection list of the Com’X 210/ 510, so user is unable to select these devices.


Product Line
Com'X 210: All firmware versions
Com'X 510: All firmware versions

Environment
ComPact NS/PowerPact P, R breakers on Com’X 210/510 network.

Cause of Issue
Com’X includes support for the MicroLogic trip units A, E, P, H which are used by MasterPact, PowerPact P, R/ComPact NS breakers. Com’ X supports the PowerPact/Compact NS breakers as MasterPact breakers. The PowerPact P, R/ComPact NS do not display in the device selection list.


Resolution
To create a PowerPact P, R/ComPact NS breaker within Com’X:
1.Select a MasterPact breaker with corresponding MicroLogic trip unit (A, E, P, H) from the Device Type drop-down list.
2.Rename it as PowerPact P, R/ComPact NS breaker.
Click Create to create the PowerPact/Compact NS device.
Create New Device setup

Schneider Electric USA

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.