How can we help you today?
On a Masterpact MTZ, how can ERMS be turned OFF if the phone that turned it ON is not available?
Product Line:
Circuit Breakers
Resolution:
There is a "force unlock" feature in the Power Device app with the following combination:
Version 3 Ecostruxure Power Device MTZ app on the phone
Version 3 firmware in control unit
Note: Version 2.12.2 and later Ecostruxure Power Commission software is able to update the control unit to version 3.
The Force unlock option in the Power Device app only disengages the ERMS function if ERMS was engaged by another smartphone. it won't disengage the ERMS function if ERMS was engaged by an external selector switch, for an external switch follow the FA408274.
See attachment with a screenshot and information from the control unit user guide.
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.