How do I program an ATV12 drive to be controlled by the VW3A1106 or VW3A1107 remote keypad?

Article available in these languages:

  • Spanish

Issue
A customer wants to control an ATV12 series drive using a VW3A1106 or VW3A1107 remote keypad.

Resolution

Follow these steps to configure the drive for keypad control:

  1. From the RDY display, press ENT.
  2. Use the Down Arrow to navigate to COnF, then press ENT.
  3. Select FULL, then press ENT.
  4. Navigate to CtL, then press ENT.
  5. Navigate to Fr1, then press ENT.
  6. Select LCC, then press ENT.
  7. Press ESC repeatedly until the display returns to RDY.

The drive is now configured for Start, Stop, and Speed Control from the remote keypad.

Starting and Stopping the Motor

  • Press Run to start the motor.
  • Press Stop to stop the motor.

Adjusting the Speed Reference

  1. From the default display (RDY when stopped or the output frequency when running), press ENT to access rEF.
  2. Press ENT again to display the current frequency setpoint.
  3. Use the Up Arrow or Down Arrow to increase or decrease the speed reference.
  4. Press ENT to save the new value, if required.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings