What are the possible long time amperage settings on a STR23SP trip unit?

Product Line:
Molded Case Circuit Breaker

Resolution:
Use formula: Desired amperage / In = In multiplier.
Then look at the table below for the In multiplier computed or the nearest multiplier.
Set the Io and Ir dials to the values corresponding the In multiplier.


Table. All possible In multipliers for all combinations of Io and Ir dials
In multiplier = Io * Ir

In multiplierIoIr
111
0.9810.98
0.9510.95
0.9310.93
0.90.91
0.910.9
0.8820.90.98
0.8810.88
0.8550.90.95
0.8510.85
0.8370.90.93
0.810.90.9
0.80.81
0.810.8
0.7920.90.88
0.7840.80.98
0.7650.90.85
0.760.80.95
0.7440.80.93
0.720.80.9
0.720.90.8
0.7040.80.88
0.70.71
0.6860.70.98
0.680.80.85
0.6650.70.95
0.6510.70.93
0.640.80.8
0.630.631
0.630.70.9
0.61740.630.98
0.6160.70.88
0.59850.630.95
0.5950.70.85
0.58590.630.93
0.5670.630.9
0.560.70.8
0.55440.630.88
0.53550.630.85
0.5040.630.8
0.50.51
0.490.50.98
0.4750.50.95
0.4650.50.93
0.450.50.9
0.440.50.88
0.4250.50.85
0.40.50.8

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings