How can we help you today?

How is the 50C rating accomplished in the Enclosed ATS22 Soft Start Controllers?

Resolution:
Engineering uses an oversized ATS22 softstart with de-rating based on temperature instead of adding a cooling fan.

Example:
ATS22C14S6U has 124 nominal motor current. We want 52C rating, so over nominal temperature (40C) by 12C.
We have a derating of 2.2% for every 1C over 40C.
52-40= 12.
12x2.2% = 26.4%.
26.4% of 124 = 32.24.
32.24 is the deduction for the 124 nominal motor current of ATS22C14S6U. So the ATS22C14S6U has only rated to 91.76A motor in 52C temperature.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings