How can motor stalling be reduced on an ATV320 besides adjusting IR compensation?

Resolution:
Motor stalling can be caused by mechanical issues with the motor or driven load, excessive load, or a speed loop that is not properly adjusted for the application.

Before adjusting the drive parameters, verify that there are no mechanical issues with the motor or driven load. Check that the motor and load can rotate freely and that there is no binding, excessive friction, blockage, or other condition that could cause excessive motor load.

If the mechanical system is operating correctly, the speed loop can be tuned based on the selected motor control type (CtT):

  • When CtT = Standard, adjust the SPGU parameter.
  • When CtT = SVCV, adjust the SPG and SIT parameters.

Proper speed loop adjustment can help improve motor response and reduce stalling. Make parameter changes carefully and verify motor operation under actual load conditions.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings