How to Refresh an Embedded List in ClearSCADA?

Published date: 15 September 2019

Here are the steps to execute the automatic refresh on the embedded list:
  1. Right-click on the created embedded list and choose properties
  2. under "General" tab click "Pick Action"

     
  3. select "Script and press next

     
  4. select Mode "Execute Code Fragmentation on Top-Level Mimic" and write the code as follows Mimic.Layers(0).Item("Lst_2").Sql = Mimic.Layers(0).Item("Lst_2").Sql

     
  5. select Next then Finish.

    Once configured, save the mimic and put it into runtime mode. If you left-click on the list, the query will update and the list will refresh automatically with the newest results displayed.
 
 