What is the maximum current rating of the P24 external power supply on an ATV340 drive?

Resolution :

The P24 external power supply terminal on the Altivar ATV340 drive is available only on Frame Size 4 and Frame Size 5 models, specifically from ATV340D30N4 to ATV340D75N4.

The electrical specifications for the P24 terminal are:

  • Maximum output current: 0.8 A
  • Allowable voltage range: 19 VDC (minimum) to 30 VDC (maximum)


Information is listed from the ATV340 Installation Manual NVE61069

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings