How to delete recipes at runtime on the Magelis HMI?

Issue:
Looking for options on how to delete recipes created or downloaded to the Magelis HMI at runtime.

Product Line:
Vijeo Designer (all versions)

Resolution:
In Vijeo Designer, there are a couple of ways in which we can delete a recipe during runtime on the Magelis HMI.

The first option is to make use of a "Delete" recipe button that you can drag onto the panel from the toolchest in Vijeo Designer. During runtime, when you select a recipe group and recipe, when you press the Delete button, it will delete the selected recipe from the list.

The second option is to write a script in an action or in a touch action script. The script will essentially write a value to the _RecipeDefaultControl.Operation variable. The value to trigger a delete is the value "16"

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings