How to resize Hierarchy Manager editor window in PME

Environment:
Power Monitoring Expert Hierarchy Manager.

Product Line:

PME 8.x, PME 9
PME 2020

Description of the issue:
In some scenarios when you use long hierarchy architecture and you have a huge list then you may see that the hierarchy editor window or each column in the editor window is not able to fit all the information.

Cause:
By default, the hierarchy editor window is not resizable

Resolution:
For PME2020, PME2020 CU1 and PME2020 CU2, kindly contact your technical support center and request Hotfix_Bug105047

For PME9 and PME8.x

Open ..\Power Monitoring Expert\Applications\HierarchyManager\Scripts\HierarchyManager

To change the behavior of the editor window open "view.nodedetails.js" using notepad ​for editing.
Update the "resizable:" parameter to "true" and save.

To change the behavior of the column in the editor window open "view.editor.reference.js" using notepad ​for editing.
Update the "resizable:" parameter to "true" and save.

You may have to restart the browser and IIS for the change to take effect.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings