How can we help you today?

Quantum application when migrated to M580 migration might reflect out of Range State RAM values


Symptoms:-

Previously it was possible to configure on Quantum (%m-65 000, %mw–40 000) State RAM values, with M580 these values overpass the 100%. Even with an empty M580 Control Expert application with configuration value (%m-65 000, %mw–40 000) the State RAM value is 120% and with an empty Quantum application and same values the State RAM value is 89%.

Resolution:-

The issue is fixed in Control Expert V14.1, State Ram % is the same as Quantum, the calculation of StateRam occupation was wrong and copied from M340., now it is corrected.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings