How can we help you today?

What is the cross for a MA-407-701-0-4 actuator ?

Issue:
Is there a replacement for the MA-407-701 actuator?

Product:
Valves and Actuators

Environment:
Maintenance

Cause:
Replacement

Resolution:
The MA-407-701-0-4 is an OEM actuator which crosses to a MA-407-701 actuator could use 120vac or 240vac , with a factory preset rotation of 113 deg. Both Actuators are obsolete and not available, but a MA-418-500 120VAC actuator, or the  MA-419-500 240VAC actuator can be used to replace it.  Rotation from the Factory is 170 deg for the MA-418, and MA-419 actuators, and would need to be field adjusted to 113 deg for an equal cross.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings