What is the cross for a MA-407-701-0-4 actuator ?

Issue:
Is there a replacement for the MA-407-701 actuator?

Product:
Valves and Actuators

Environment:
Maintenance

Cause:
Replacement

Resolution:
The MA-407-701-0-4 is an OEM actuator which crosses to a MA-407-701 actuator could use 120vac or 240vac , with a factory preset rotation of 113 deg. Both Actuators are obsolete and not available, but a MA-418-500 120VAC actuator, or the  MA-419-500 240VAC actuator can be used to replace it.  Rotation from the Factory is 170 deg for the MA-418, and MA-419 actuators, and would need to be field adjusted to 113 deg for an equal cross.