Control Expert returns 'license management brick could not be loaded successfully'.

Issue
Control Expert returns 'license management brick could not be loaded successfully' after installing the MC80 hotfix.

Product Line
Control Expert 14.1

Environment
Windows 7 64 bit

Resolution
Control Expert returns the error 'license management brick could not be loaded successfully' after installaing the MC80 hotfix,

This could occur if the MC80 hotfix was not correctly installed. During the installation, the 'Microsoft Visual C++ 2012 Update 4
Redistributable Package (x86)gets installed. If the installation fails, the issue will occur.

To resolve the issue:

  • Uninstall Control Expert.
  • Reboot the PC.
  • Run a registry cleaner.
  • Install of Control Expert XL V14.1.
  • Run Control Expert.
  • Install 'New Ethernet Module Limitation Hot Fix'
  • Run Control Expert.
  • Installed MC80 Hotfix for Control Expert 14.1

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings