How can we help you today?

How to Update the Application for the Vigilohm IMDLRDH

Note: Implementing a new application in your IMDLRDH will erase your previous configuration.

To update the application program of your IMDLRDH you need to:

Have a formatted USB Pen Drive in FAT32 format.

Unzip the content of application zip file and place the extracted files on the root of your USB Key.

Image showing the extracted application file in root of the USB Drive

Switch off the IMDLRDH

Plug the USB Key in the USB port of the IMDLRDH

Image showing USB port of IMLRDH where the USB Drive needs to be inserted

Power on the IMDLRDH, wait until the installation confirmation screen appears.

Image showing the confirmation to install the application file

Press Yes to Start the installation.

Device will restart and installation will start automatically.

Image showing the installation progress

Wait for the program to be installed completely in the IMDLRDH

Once installation is complete this screen will appear.

Image showing the installation is complete

Remove the USB Pen Drive and click restart.

After these steps you need to perform the commissioning of your IMDLRDH.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings