How many shunt trip (and shunt close) devices can be installed on a Masterpact NW?

Issue:
How many open and close coils can be installed on an NW breaker?

Product Line:
Circuit Breakers

Resolution:
An NW breaker can accept one or two shunt trips and only one shunt close. If a UVR is installed, only one shunt trip can be installed.