How can we help you today?

Are the Masterpact NW and NT shunt trip and shunt close coils continuous duty rated?

Issue:
Does the Masterpact NW shunt trip and shunt close have a coil clearing switch?

Product Line:
Masterpact NT and NW breakers

Resolution:
Yes, the coils themselves are continuous duty rated and do not use a coil clearing switch. However, in actual use, a maintained signal should not be used on the shunt close coil (XF). Any opening order will open the breaker so a standing close order is not necessary. Instead, use a signal of at least 200 ms on the shunt close coil (XF) then remove the signal.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings