How can we help you today?

What are the repair parts for an HOM40L200RB, series 2 load center?

Product Line:
Load Centers

Resolution:
Only the parts listed below are considered field replaceable:
Cover - 4055802205
Cover Mounting Screws - 2142717161
Interior Trim - 4055825101
Interior Trim Mounting Screw - 4020513001K
Interior Assembly - HOMN40L200
Neutral Bonding Screw - 4020512201
Main Lug - 4025104451
Note: Covers and Interior Trims do not have labels applied.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings