What does the endurance test consist of that a UL489 circuit breaker must pass?
Issue:
What is the endurance rating for the thermal magnetic breakers?
Product Line:
Circuit Breakers
Resolution:
Circuit breakers are tested to UL489 and CSA 22.2. For endurance, both thermal-magnetic and electronic circuit breakers must successfully complete the number of operations shown in the below table.
NOTES:
Circuit breakers are not tested until they fail, so the maximum number of operations is not known.
Environmental factors affect the life of a breaker, so the number of test operations in the table should not be interpreted as a guaranteed number in actual use.
What is the endurance rating for the thermal magnetic breakers?
Product Line:
Circuit Breakers
Resolution:
Circuit breakers are tested to UL489 and CSA 22.2. For endurance, both thermal-magnetic and electronic circuit breakers must successfully complete the number of operations shown in the below table.
- Power factor shall be 0.75 to 0.80 lagging.
- Starting in the open position, the breaker is closed, then opened (this counts as one operation)
- The Full Load Operations Test is done at rated current and voltage
- The No Load Operations Test is done following the Full Load Test
| Frame Size in Amperes | Full Load Operations | No Load Operations |
| 0-100 | 6,000 | 4,000 |
| 101-225 | 4,000 | 4,000 |
| 226-600 | 1,000 | 5,000 |
| 601-800 | 500 | 3,000 |
| 801-2500 | 500 | 2,000 |
| 2501-4000 | 400 | 1,000 |
NOTES:
Circuit breakers are not tested until they fail, so the maximum number of operations is not known.
Environmental factors affect the life of a breaker, so the number of test operations in the table should not be interpreted as a guaranteed number in actual use.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.