Can a key interlock be used on an I-line panel with a vertically mounted main breaker?
Issue:
Do we have an interlock for I-line vertically mounted main breakers and a branch breaker?
Product line:
Panelboards
Environment:
Vertically mounted main breakers in I-line panelboards
Resolution:
No. All I-Line key interlocked breakers must be located in the branch portion of the I-line panel between a backfed main and a branch breaker. A special mounting bracket is used to mount the interlock. There isn`t a location for this bracket with a vertically mounted main breaker application.
Do we have an interlock for I-line vertically mounted main breakers and a branch breaker?
Product line:
Panelboards
Environment:
Vertically mounted main breakers in I-line panelboards
Resolution:
No. All I-Line key interlocked breakers must be located in the branch portion of the I-line panel between a backfed main and a branch breaker. A special mounting bracket is used to mount the interlock. There isn`t a location for this bracket with a vertically mounted main breaker application.
Released for: Schneider Electric USA