What Class of fuses do the D211N and D211NRB General Duty safety switches accept?
Issue:
Application
Product Line:
GD SS
Cause:
Fuse selection
Resolution:
This switch accepts ``Edison Base`` plug type fuses only, size E26, 30A max. The switch is UL listed for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current.
Application
Product Line:
GD SS
Cause:
Fuse selection
Resolution:
This switch accepts ``Edison Base`` plug type fuses only, size E26, 30A max. The switch is UL listed for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current.