How many terminals do the equipment ground kits PKOGTA4, PKOGTA6, PKOGTA7, and PKOGTA8 have and what wire sizes do they accept?
Issue:
Product Design Features
Product Line:
Heavy Duty Safety Switches
Resolution:
1) The PKOGTA4 has 4 separate lugs in the kit and each lug will accept (1) #6 - 250 kcmil Al/Cu conductor
2) The PKOGTA6 has 6 terminals and each terminal will accept (1) #14 - #1/0 Al/Cu conductor
NOTE: the PKOGTA6 contains 1 ground bar with the 6 holes and is approximately 4.61 inches long
3) The PKOGTA7 has 8 terminals and each terminal will accept (1) #4 - 350 kcmil Al/Cu conductor
NOTE: the PKOGTA7 contains 2 ground bars, each bar has 4 holes and is approximately 5.50 inches long
4) The PKOGTA8 has 8 terminals and each terminal will accept (1) #4 - 350kcmil Al/Cu conductor
NOTE: the PKOGTA8 contains 2 ground bars, each bar has 4 holes and is approximately 5.50 inches long
Product Design Features
Product Line:
Heavy Duty Safety Switches
Resolution:
1) The PKOGTA4 has 4 separate lugs in the kit and each lug will accept (1) #6 - 250 kcmil Al/Cu conductor
2) The PKOGTA6 has 6 terminals and each terminal will accept (1) #14 - #1/0 Al/Cu conductor
NOTE: the PKOGTA6 contains 1 ground bar with the 6 holes and is approximately 4.61 inches long
3) The PKOGTA7 has 8 terminals and each terminal will accept (1) #4 - 350 kcmil Al/Cu conductor
NOTE: the PKOGTA7 contains 2 ground bars, each bar has 4 holes and is approximately 5.50 inches long
4) The PKOGTA8 has 8 terminals and each terminal will accept (1) #4 - 350kcmil Al/Cu conductor
NOTE: the PKOGTA8 contains 2 ground bars, each bar has 4 holes and is approximately 5.50 inches long
Released for: Schneider Electric USA
Explore more
Product:
Explore more
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.