How can we help you today?

Can you install a QO-GFI, QO-CAFI, QO-DF, or QO-EPD breaker in a QO24L70F, QO24L70S, or QO24L70RB load center?

Issue:
Application

Product Line:
QO LC

Resolution:
Yes. When using an electronic branch breaker, the QO24L70F, S, or RB has adequate wire bending space for a maximum #10 AWG wire. This will restrict the QO-GFI and QO-EPD breakers to a maximum of 30 amperes.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings