Can a 2p, QO-GFI branch breaker be used in a QO24L70F, QO24L70S, QO2L40RB, or QO24L70RB load center?

Issue:
Product features

Product Line:
QO load centers

Resolution:
Yes, but those load centers only have adequate wire bending space for a maximum #10 AWG wire. This will restrict the QO-GFI breaker to a maximum of 30 amperes.