What is the length of probe for 9025GXW3 temperature switch?<br /><br />
Issue:
9025GXW3 probe's length
Product Line:
Relays and Timers
Environment:
Class 9025 Temperature Switch
Resolution:
3 inches
9025GXW3 probe's length
Product Line:
Relays and Timers
Environment:
Class 9025 Temperature Switch
Resolution:
3 inches
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.