How do you replace a coil on an 8910DPA92 contactor?

Issue:
What are the instructions to remove the coil on a DPA9* Contactor?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
Class 8910 Type DPA Contactors

Resolution:
Loosen and remove the four screws on the back of the contactor. Take the back off and set it aside. Remove the E-shaped magnet. Take the coil out and drop a new coil in its place. Reverse the above procedure.