Does the rating plug need to be removed for hi-pot or dielectric testing on breakers with the P and H trip units?

Issue:
Does the rating plug need to be removed for hi-pot or dielectric testing on breakers with the P and H trip units?

Product Line:
Micrologic

Resolution:
Yes. But it is not necessary to remove the rating plug on the basic and A trip units.

Dielectric tests (high potential, insulation resistance, or Megger tests) may damage Micrologic® P and H trip units.
• Remove rating plug from trip unit prior to testing.
• Replace trip unit if rating plug was not removed during tests or if trip unit was exposed to more than 700 Vac.
Failure to follow these instructions can result in equipment damage.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings