How can we help you today?

What is the interior trim kit for the HC3273WP?

The following parts are required:
(12) 80025-067-01 screws
(2) 80106-252-04 end trims
(2) 80106-251-08 side trims

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.