What is the rating of the number of switching operations of Square D, 100 A, heavy duty, F-Series safety switches?

Issue:
100A, Heavy Duty, F-Series Safety Switches, number of switching operations.

Product Line:
Safety Switch

Resolution:
For Safety Switches, the standard for design and testing of the number of switching operations is governed by UL98 and NEMA KS-1. There are two separate tests: (1) Endurance Test, and (2) Horsepower-overload test. The table below shows the minimum number of operations required (OFF to ON to OFF) by UL and NEMA. For the endurance test, however, Square D 100A F-Series Safety Switches exceed the UL and NEMA requirements by more than 3 times the total (see the table below):

100A, Square D Heavy Duty Safety Switches (F-series)
Endurance Test - Number of OperationsHP Test - Number of Operations
Test StdsRated Load*No LoadTotal (Load + No Load)at rated HP**
UL600040001000050
NEMA700070001400050
Square D7000430005000050

* Endurance test performed at switch rated load current
** Horsepower test - make/break motor inrush/locked rotor current at rated HP

Number of switching operations for other Heavy Duty Safety Switches:
For 30-60A series F Heavy Duty safety switches, see FA99746
For 200A series F Heavy Duty safety switches, see FA99791
For 400A series E Heavy Duty safety switches, see FA99792
For 600A series E Heavy Duty safety switches, see FA99819
For 800A series E Heavy Duty safety switches, see FA99821
For 1200A series E Heavy Duty safety switches, see FA99822

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings