Are general duty safety switches suitable for use as service equipment?
Issue:
Product design features
Product Line:
General Duty Safety Switches
Resolution:
Most general duty switches are suitable for use as service equipment when equipped with a factory or field installed neutral assembly or a field installed service grounding kit.
NOTES:
1) The following general duty safety switches DO NOT have solid neutral assemblies that can be used in the switch: DU321, DU321RB, DU322, DU322RB, and DU325. If a neutral is required, consider using a heavy duty switch.
2) If the switch is older and already installed, CHECK the wiring diagram to see if it shows a solid neutral assembly or service/equipment ground kit part number. If NOT, then it doesn't allow or have a solid neutral or ground kit that can be installed.
Product design features
Product Line:
General Duty Safety Switches
Resolution:
Most general duty switches are suitable for use as service equipment when equipped with a factory or field installed neutral assembly or a field installed service grounding kit.
NOTES:
1) The following general duty safety switches DO NOT have solid neutral assemblies that can be used in the switch: DU321, DU321RB, DU322, DU322RB, and DU325. If a neutral is required, consider using a heavy duty switch.
2) If the switch is older and already installed, CHECK the wiring diagram to see if it shows a solid neutral assembly or service/equipment ground kit part number. If NOT, then it doesn't allow or have a solid neutral or ground kit that can be installed.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.