How can we help you today?

How do I remotely initiate a transfer to Emergency on a series 300 with Group G controller?

You can send "remote transfer to emergency" signals via the External Feature 17 contacts.

External Feature 17 contacts are located on the Series 300 Group G controller.  The terminals for the External Feature 17 are TB1-8 and TB1-9.  Refer to the ATS wiring diagram.

Connect a Normally Closed set of contacts across the terminals.  Opening the contact will cause the generator to start and run, and transfer to Emergency side once the ATS controller recognizes the Emergency source as an acceptable source.

Before opening the contacts, make sure to enable the Ext. Feature 17 in the ATS controller first.





Enable the External Feature 17 via the Group G controller.  Make sure there is a CHECK mark on the box corresponding to Ext Feature 17 to ENABLE it.  Refer to the Group G Controllers User Guide.



If unsure, contact Technical Support at 1-800-800-ASCO or send an email to technicalsupport@ascopower.com

You may also watch the video related to this (please see below).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings