Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can ATV630 date and time be adjusted "remotely" with SoMove?

The drive date and time can not be set remotely through SoMove, however possible through the Webserver.

For that, you should set a SNTP server on the webserver page to have an automatic update of the date and time.

The second possibility will be set the date and time on a first drive equipped with a graphic display terminal.

Dates and time of others drives will be updated when the graphic display terminal of the first drive will be plugged on them.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings