Can ATV630 date and time be adjusted "remotely" with SoMove?

The drive date and time can not be set remotely through SoMove, however possible through the Webserver.

For that, you should set a SNTP server on the webserver page to have an automatic update of the date and time.

The second possibility will be set the date and time on a first drive equipped with a graphic display terminal.

Dates and time of others drives will be updated when the graphic display terminal of the first drive will be plugged on them.