Issue:
Are the drive Relay contacts rated for 120Vac?
Resolution:
Yes, the drives relay contact R1 is rated for AC and DC voltage.
R1A NO contact of relay R1
R1B NC contact of relay R1
R1C Common point contact of relay R1
Output Relay 1
Minimum switching capacity: 5 mA for 24 Vdc
Maximum switching current on resistive load:
3 A for 250 Vac (OVC II) and 30 Vdc
Maximum switching current on inductive load:
2 A for 250 Vac (OVC II) and 30 Vdc. Inductive load must be
equipped with a voltage surge suppression device according to ac or
dc operation with total energy dissipation greater than the inductive
energy stored in the load. Refer to sections Output Relay with
Inductive AC Loads and Output Relay with Inductive DC Loads
Refresh time: 1 ms ± 0.25 ms
Service life: 100,000 operations at maximum switching current
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA



