How can we help you today?

Masterpact MTZ: Components needed to locally operate breaker via smartphone app

Issue: Local operation via phone app capability was not ordered from the factory.  Need to field modify.
Product Line: Circuit Breakers
Environment: Masterpact MTZ

Resolution: to field modify, the following components are required. Some of these parts may already be installed.

  • Mobile App – EcoStruxure Power Device
  • Masterpact Operation Assistant Digital Module LV850005
  • XF-Com, MX-Com coils, part numbers vary based on voltage.
  • Spring Charging Motor, part numbers vary based on voltage.
  • Isolation Module LV850056SP

Isolation module

  • Isolation Module to coils communication cables MTZ1: LV833118SP, MTZ2/MTZ3: LV847904SP

isolation module to coil cables

  • MX-Com cable needs to be plugged into the MX1 location on Isolation module, not MX2.

Isolation module MX1 wiring location

  • Coils properly wired, C3 and A3 continuously powered. C2 and A2 are only needed for push button operation.

coil wiring diagram

  • Accessories Declared in the Control Unit via EPC, click the accessory pencil

edit breaker accessories


Then declare accessories
declare accessories

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings