How can we help you today?

Do the QO and HOM circuit breakers accept copper-clad aluminum (CCA) conductors?

Issue:
Will all or any QO and/or HOM miniature circuit breakers accept copper-clad aluminum wires?

Product Line:
Miniature Circuit Breakers

Resolution:
In the US, yes. Per UL 489, miniature circuit breakers and wire connectors marked Al/Cu or Cu/Al may be used with copper, aluminum, and copper-clad aluminum conductors. Associated marking for conductor type and wire size will be on the face of the circuit breaker or the label above the lugs. In Canada and Mexico, construction with copper-clad aluminum (CCA) conductors is not allowed.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings