COMMUNICATION ARCHITECTURE: Single ATS connected to one (QEM) connectivity module
Note:
- QEM - Quad-Ethernet Module
- ASCO 5140 connectivity module for Group G controller
- https://asco-power.cld.bz/ASCO-Power-Technologies-Products-Digital-Binder/323/
- ASCO 5170 connectivity module for Group 5 controller
- https://asco-power.cld.bz/ASCO-Power-Technologies-Products-Digital-Binder/315/
- ASCO 5140 connectivity module for Group G controller
ASCO 5310 Remote Annunciator
ASCO 5350 Remote Annunciator
1. Log in to the built-in web interface.
- Open a web browser and in the address bar, type in the default address http://169.254.1.200
- Refer to manual 381333-315 for details of the log in credentials
- Highly recommended that you change the password
3. Select Single ATS and press the corresponding Go button under the selection.
A. Automatic ATS Configuration:
1. The auto discovery of the ATSs, enter the IP address of the QEM to which the ATS is connected.
2. Select the check boxes next to each ATS.
3. Then click Automatic.
4. Pop-up window will show to show complete discovery.
B. Manual ATS Configuration
1. To manually configure the ATSs click Manual
2. Click Enable, enter the ATS Name, and the IP Address. On the Controller/ Protocol list, Controller Address, and PM Address, select the appropriate settings.
3. Click Save.
Refer to this link for the installation manual:
https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=asc-pcm-um-5350.pdf&p_Doc_Ref=PCM-UM-5350ATSRA