How can we help you today?

What Replacement Parts Are Required for a Faulty Hand‑Off‑Auto Selector on an ATV660 Drive?

Resolution:
If the Hand‑Off‑Auto (HOA) selector on an ATV660 drive is not working or is damaged, the following replacement parts are required.

Required Replacement Parts:

  • (1) ZB5AD3 – Selector switch head
  • (1) ZB5AZ103 – Selector switch body
  • (2) ZBE102 – Contact blocks
  • (1) ZBZ32 – Legend holder
  • (1) 65170-166-17 – Legend plate

These parts are available through Schneider Electric distributors.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings