What is a CLF fault on the ATS48 starter?

CLF (Control Line Failure)

The CLF fault indicates a Control Line Failure. The ATS48 monitors the control voltage supplied to terminals CL1 and CL2 on the control unit.

This fault is relatively uncommon and is typically caused by a transient loss or drop in the control voltage. For a CLF fault to occur, the voltage on CL1-CL2 must fall below the specified threshold for a sufficient duration.

CLF Fault Thresholds

  • ATS48...Q models: Voltage drops below approximately 88 V (40% of 220 V).
  • ATS48...Y models: Voltage drops below approximately 44 V (40% of 110 V).

Possible Causes

  • Loss of control voltage at terminals CL1-CL2 for at least 200 ms.
  • Control voltage falling below the specified threshold.
  • Poor power quality or intermittent supply issues.

Recommended Troubleshooting

  1. Measure the voltage at terminals CL1 and CL2 and verify that it remains within the acceptable operating range.
  2. Check the quality and stability of the incoming control power supply.
  3. If the control voltage is stable and within tolerance, the issue may be related to the power board, in which case replacement of the power board should be considered.

Because this fault is often caused by a temporary voltage dip, it is important to verify the stability of the control power source before replacing any components.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings