How can we help you today?

Upgrading M580 Safety to 3.20 causes SDI and SDO failure

Issue

After upgrading the M580 Safety CPU to version 3.20 the BMXSDI1602 and BMSDO0802 IO modules went into failure.

Product Line

M580 Safety Controllers, Control Expert

Resolution

When using BMECRA31210 modules along with CPUs having 3.20 or greater firmware, the CRA must be at version 2.60 minimum.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings