Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error

Issue
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
1
Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....

  1. Delete the content of Standby IO Server Name column or configure correct IO Server name in equipment.csv file. and save it.

2

  1. Make sure the package received from EPAS-E contains only one OIS HMI and not multiple HMI as below.

3

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings