How can we help you today?

How to set up Somove to connect to a ATV340 Drive using CANopen.

Issue:

How can you connect Somove using the CANopen connection option?

Product Line:

ATV61, ATV71, ATV320 and ATV340 only

Environment:

All

Cause:

Connection using CANopen

Resolution:

You will need to use a CANopen USB-CAN Dongle ( Port 1 only is supported) if you have a dual port.

This connection option is only supported with the ATV61, ATV71, ATV320 and ATV340 Drives only. You can not use this option on the ATV630 or ATV930 drives.

See the attached document on setting up Somove to use CANopen.

Schneider Electric USA

Attachment(s)
SoMove CANopen connection instructions.pdf [674.32 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings