If the LED blinking pattern has stopped on an AF or AFGF breaker, can it be re-initiated to determine the last trip?

Product Line:
QO and HOM arc fault and dual function breakers

Resolution:
There are two ways to re-initiate the LED blinking pattern:
1) Do a quick press and release of the test button (holding down will trip the breaker)
2) The LED will re-initiate its blinking pattern when the breaker is turned on