Where is an S-Flex run contact wired for Auto mode?
The ATV212 S-Flex enclosed drive is a product built and sold for the US HVAC market.
It had very limited options to select when ordering.
All followed a standard set of drawings which are included in the S-Flex Instruction Bulletin: https://www.se.com/us/en/download/document/30072-451-83/
The S-Flex models without bypass use a dry contact wired between terminals P24 and F to manage the Start/Stop of the system. This is a 24Vdc circuit.
The S-Flex models with bypass use a dry contact wired between terminal 5 and 6 to manage the Start/stop. This is a 120Vac circuit.
***********************